Generator Monitoring: Remote Monitoring of Voltage, Fuel Levels, and Malfunctions

Remote monitoring of a generator set: voltage, current, frequency, fuel level, operating hours, and failure alerts.

Quick answer
The monitoring of a generator set monitors in real time the voltage, the current, the frequency, the fuel level and the operating hours from a cloud platform. Instant alerts for outages, low fuel levels, or startup failures allow you to take action before any service interruptions occur at your critical sites.

Why Monitor a Generator Remotely?​

A backup generator is, by definition, a piece of equipment that must start up the very moment everything else fails. A generator that fails to start during a power outage has failed in its mission, potentially with serious consequences (hospitals, data centers, pumping stations, telecom towers).

Paradoxically, backup generators are often the least closely monitored pieces of equipment: they are located in utility rooms, are rarely started up, and their failure is not discovered until the next power outage. Remote monitoring radically changes this situation.

Key Metrics Monitored​

Electrical (Alternator)

  • Voltage per phase (L1, L2, L3): detection of imbalance or under/overvoltage
  • Current per phase: detection of overload or load imbalance
  • Frequency: 50 Hz ± 2% for sensitive applications
  • Active power (kW) and reactive power (kVAR): load monitoring
  • Energy generated (kWh): billing or reporting

Diesel Engine

  • Fuel level (liters and %) with range calculation
  • Oil pressure (bar): alarm if < minimum threshold
  • Coolant temperature (°C): overheating alarm
  • Starter battery voltage (V): faulty battery = engine won’t start
  • Engine RPM: check for proper acceleration

Controller and Control

  • Mode (automatic / manual / off)
  • Grid/generator set coupling status (ATS position)
  • Controller alarm codes (via Modbus)
  • History of starts and durations

Monitoring Architecture for a Fleet of Generators​

ComponentRole
Field SensorsMeasures fuel level, current, and temperature
Generator Set Controller (DSE/ComAp)Centralizes engine and alternator measurements
4G IoT GatewayReads data from the controller via Modbus, transmits it to the cloud
Cloud PlatformDashboards, alerts, reports, remote control
On-Call SupportReceives SMS/email alerts in the event of a malfunction

Use Case: Multi-Operator Telecom Sites​

Base stations (BTS, NodeB, eNodeB) are always equipped with a backup generator to ensure uninterrupted service in the event of a power outage. A national telecom operator manages thousands of sites under strict constraints:

  • Fuel: Some sites consume 15 to 20 L/h and can run out of fuel within 24 hours if the outage lasts that long.
  • Starting battery: Silent failure until the next outage.
  • Periodic tests: required by specifications, but often poorly documented.

Centralized monitoring allows a team of 3 to 5 people to oversee more than 500 sites and trigger targeted fuel replenishments only where necessary, rather than conducting systematic rounds.

Alerts and Escalations​

A properly configured alert system distinguishes between:

  • Warning: Fuel at 60%, battery at 24 V (voltage normal but requires monitoring).
  • Alert: Fuel at 30%, generator in minor alarm (on-call staff notified).
  • Critical alarm: Generator fails to start, fuel at 10%, engine temperature > 100 °C (automatic phone call to the night on-call staff).
  • Escalation: If the on-call staff does not respond within 15 minutes, the technical manager is contacted.